How to test a ball valve — shell, seat and cavity, and the four traps that spoil the reading

A ball valve looks like the easiest valve to put on a bench and it is the one that most often produces a reading somebody has to repeat. The ball moves, the body traps air, the cavity holds water, and a three-piece body does not like being squeezed. This page is the sequence we recommend for floating, trunnion and double block and bleed ball valves: what to pressurise, where the ball has to sit, how to read a seat that only seals once pressure arrives, and what to fix before the next valve goes on.

Ball valvesShell 1.5 × ratingSeat 1.1 × ratingBoth seats, both directions

Get a quotation  Send your DN range + PN class

Quick answer

Shell test1.5 × rating, ball partly open
Seat test1.1 × rating, ball fully closed, each side in turn
Cavity testOnly when the purchase specification asks for it, through the body plug
MediumWater for shell; air for a gas seat test
Air ventingAt the highest point of the body, never through the bore
BenchVertical to DN300, horizontal for long-pattern and DN350+
After the testCavity drained and dried before the valve leaves the bench

Three tests, not one

The phrase “test the ball valve” hides three separate operations with three different objects under pressure. They are run one after the other on the same bench, and each one produces its own record line. Skipping one of them is the usual reason a valve passes here and fails at the end user's site.

TestWhat is under pressureBall positionWhat you read
ShellBody, bonnet, both seat retainers, body jointPartly openBody porosity, joint seepage, stem packing
Seat, side AUpstream half, one seatFully closedLeakage at the open (downstream) end
Seat, side BThe other half, the other seatFully closedLeakage at the now-open end
CavityThe space between two closed seatsClosed, cavity isolatedCavity leak, and whether the body plug holds

A ball valve has two sealing faces with a single moving part between them. Testing “the valve” as one object gives one number and hides which of the two seats failed — and on a floating ball design the two seats are proven under completely different mechanical conditions, as the next sections show. The cavity row only applies to a double block and bleed valve, where two seats trap a volume of product in the middle; on a standard single-seat arrangement there is nothing to isolate.

Trap 1 — the air has nowhere to go

Water entering a closed ball valve meets two air pockets: the bore between the two seats, and the space in the body neck above the ball. Both compress. On the shell test the gauge then reads stored energy rather than a settled pressure, and when the pressure is released the pocket expands and pushes water back out of the vent — which reads as a leak in the wrong place at the wrong moment. On the seat test the damage is worse: a pocket on the downstream side escapes past the seat as a continuous bubble stream that has nothing to do with the seat face.

The fix is mechanical, not procedural discipline. Fill slowly, and fill with the valve oriented so that its own vent or drain plug is the highest point on the body. Open that plug while filling and close it the moment water appears. On a vertical bench with a long-pattern valve, the plug often ends up on the low side — in that case fill through the plug itself, or clamp the valve rotated, rather than relying on the operator to remember a purge step. Where the valve has no body plug, the only vent is the open end, so the seat test has to be run with the downstream side open to atmosphere and the filling done before the ball is closed.

For a gas seat test, vent the upstream side before pressurising and allow the reading to settle. An air test reaches a steady bubble rate after the initial expansion, not in the first second, and a reading taken too early is always pessimistic.

Trap 2 — the ball position rule

Shell test first, with the ball partly open. The pressure then reaches both halves of the body, both seat retainers and the body joint — the parts the shell test exists to prove. Test with the ball fully closed and the upstream seat carries the load, the downstream half of the body stays at atmospheric, and a leak past that seat is hidden inside the test itself. A partly open ball is also the position in which a body casting defect behind a seat can actually be seen.

Seat test second, with the ball fully closed. A ball sitting a few degrees off centre crosses the seal line at the edge of the bore and weeps there; the operator reads a seat failure that is really a positioning failure. Two things cause it on a bench: a lever resting against a stop, and an actuator left mounted and unpowered. Leave the lever on — the valve should be operated as shipped — but keep it clear of anything it can lean on, and on an actuated valve make sure the actuator cannot take up load while the seat is under test.

Never run a seat test with the ball half open. The seal line then runs across the edge of the bore, the seat is loaded on a line instead of a ring, and the result means nothing in either direction.

Trap 3 — clamping a body that was not designed to be squeezed

A ball valve is clamped on its end connections, and the body in between is a pressure vessel, not a fixture. Four constructions need a decision before the valve goes on the plates:

The three clamping methods compared here apply to ball valves as they do to gate valves; what changes is that the load path has to stay out of the body joints.

Trap 4 — water left in the cavity

A double block and bleed valve holds water in the cavity after the test, and a trunnion valve holds it around the seat assemblies. If it is not drained through the body plug and blown dry, it stays there: it attacks stainless trim while the valve sits in packing, it drips out of the drain plug on the customer's floor, and in a winter shipment it freezes. Put the drain and dry step on the bench record as a line to sign, not as a habit — it is the step that disappears at the end of a shift.

Reading the seat leakage when the seal is made by pressure

This is the part of ball valve testing that produces the most false rejects, and it comes from the design rather than from the bench.

Floating ball

On a floating ball the ball is free to move a millimetre or two between the seats, and the differential pressure is what pushes it into the downstream seat to seal. At the seat test pressure that force is present, so the reading is meaningful. At a very low pressure it may not be: a floating ball that weeps at a fraction of its rating and holds at 1.1 × rating is behaving exactly as designed. Recording that low-pressure weep as a failed seat rejects a good valve — and accepting it as a pass at 1.1 × is the correct reading, because that is the pressure the standard names.

Trunnion-mounted

A trunnion ball is held on bearings and does not move, and each seat has its own spring or piston assembly. A spring-energised seat seals independently of line pressure, which is why this construction is specified where the valve has to hold at low pressure or in gas service. Both seats are still independent and both still have to be tested, one direction at a time.

Soft seat and metal seat

A soft seat (PTFE, RTFE, nylon) reads against a small allowance, and it is also the seat that suffers if it is pushed above the pressure the order names. A metal seat reads against a larger allowance and the reading is taken across the full hold, because a metal-to-metal pair beds in rather than sealing instantly. The allowed number comes from the class table in the standard on the order — the leakage rate classes page maps API 598, ISO 5208 and GB/T 13927 against each other so the same valve is not judged twice by two different tables.

Air or water for the seat test

Water is the default medium and air is what an order asks for when a gas seat test is specified. Air finds smaller leaks and it is unforgiving about preparation: the seat face and the downstream bore have to be dry, and any water left in the body masks the bubbles. See the general hydrostatic sequence for the filling and holding conventions that apply to every valve family.

The sequence, step by step

  1. Identify the valve before it is clamped. Floating or trunnion, soft or metal seat, single seat or double block and bleed, one-, two- or three-piece body, end connection. Each answer changes a step below.
  2. Read what the order says. Standard and edition, pressure class, hold time, test medium, and whether a cavity test is required. The class on the order — not the class someone remembers — sets both pressures, which is why the PN to test-pressure table is worth having next to the bench.
  3. Set the ball partly open and mount the valve on the plates or adaptors, clamped on the end connections only. Lever on and free of any stop. Vent and drain plugs identified and reachable.
  4. Fill slowly and vent at the highest body point until water appears, then close the plug. Confirm the gauge has settled before the next step.
  5. Shell test at 1.5 × rating. Raise in steps, hold for the time the standard's table names, and inspect the body joint, the seat retainers and the stem packing. A drop here is a body or joint issue and the seat test has not started yet.
  6. Seat test, side A. Ball fully closed, pressure on one side only at 1.1 × rating, reading taken at the open end. Count bubbles for air, collect or count drops for water.
  7. Seat test, side B. Release, reverse the pressure, repeat. Two readings, two record lines — one pass is not a result.
  8. Cavity test if the specification asks for it: both seats closed, cavity isolated, pressure applied through the body plug, and the plug itself checked for seepage.
  9. Release, drain, dry, record. Cavity plug open, air through the body, plugs refitted, readings signed. The record is what the customer's inspector will ask for, which is why the export and record functions matter more than they look on a quotation.

What the bench has to have for ball valves

RequirementWhy a ball valve forces it
Two gauge rangesA 0–40 MPa gauge cannot read a 1.6 MPa seat test with any resolution; a low-range sub gauge is the only way to hold both in one bench
Air circuitFor the gas seat test the order asks for; water cannot be substituted silently
Access to the body plugsThe vent and drain have to be operable with the valve clamped, or the cavity never gets emptied
Drip tray at the open endThe seat test discharges at the open end by design; the floor should not be the collector
Daylight for long patternClear span, not tonnage, is what a long-pattern or three-piece body needs
Plate sets by facingRaised face, ring joint and weld-end adaptors are separate parts, and they are the cheapest thing to plan at quotation stage
Timer and recordHold times and both seat readings per valve — the format the inspector reads

Which bench for which ball valve

These are the catalogue envelopes; a ball valve sits inside them like any other valve of the same bore and class, with the fixture decision coming from the end connection.

ModelDN rangeTest pressureWhere it fits a ball valve programme
SYJ-150DN15–DN1500–40 MPaSmall ball valves at high class in a repair or assembly shop
ZSYJ-300ADN50–DN3001.6–40 MPaGeneral repair covering several classes on one bench
SYJ-600SQDN50–DN60040 MPa water / 4 MPa airWater shell and seat plus the air seat test without a second station
SYJ2-300-600DN50–300 and DN350–600PN6–PN100Small and large ball valves in the same shift
WBD-600DN50–DN6000–16 MPaLong-pattern and heavy trunnion bodies that have to lie flat

Boundaries worth writing down

The bench does not declare the valve compliant. It produces a pressure record and a leakage observation. Whether that satisfies API 598, ISO 5208 or GB/T 13927 is a judgement made by your quality function or the inspector named on the order.

Torque is a different test. Break and running torque of an actuated ball valve are measured with a torque cell; a standard bench does not produce that number, and fitting one is a quotation item.

Fire-safe, cryogenic, anti-static and fugitive-emission tests are not hydrostatic tests. They are run to their own standards and cannot be inferred from a water test that passed.

Cavity relief is a valve design feature. The bench can prove that the cavity holds pressure and that the body plug seals; it cannot prove that a self-relieving seat is set correctly. That belongs to the valve maker's design verification.

The envelope is mechanical. A 40 MPa bench does not become a 60 MPa bench through software, a larger pump or a different gauge.

Questions we get asked about ball valves

Should a ball valve be open or closed for the shell test?

Partly open. With the ball open the pressure reaches both halves of the body, both seat retainers and the body joint — the parts the shell test is meant to prove. With the ball closed the upstream seat carries the load, the downstream half stays at atmospheric, and a leak past that seat hides inside the test. Fully open is also acceptable, but partly open keeps the ball away from the seat faces while the body is loaded.

My floating ball valve weeps at low pressure but holds at 1.1 × rating. Is it a failure?

No. On a floating ball the differential pressure is what pushes the ball into the downstream seat, so at very low pressure there may be nothing to make the seal. The reading that counts is the one taken at the pressure the order names. A valve that holds at 1.1 × rating and weeps below it is behaving as designed. Trunnion valves with spring-energised seats are the construction specified when low-pressure tightness is the requirement.

Can I clamp a three-piece ball valve across the body?

No. The centre section is bolted through two body joints, and clamping across it compresses those joints and can distort the seat pockets — the valve then leaks on the bench and holds in service, or the reverse. Clamp the end caps or end connections. On a long-pattern body the clear span between the plates, not the clamping force, is what decides whether the valve fits the bench at all.

How do I get the trapped air out of the body?

Fill slowly with the valve oriented so that its own vent or drain plug is the highest point, open the plug while filling, and close it when water appears. If the plug ends up on the low side, fill through the plug itself or rotate the valve in the fixture. Blowing the air out through the bore does not work on a closed valve, and on the seat test an air pocket on the downstream side shows up as bubbles that have nothing to do with the seat.

Does a double block and bleed valve need a cavity test?

Only if the purchase specification asks for one. The cavity between the two seats is a real pressure boundary and the test is run with both seats closed and the cavity isolated, pressurising through the body plug. Whether a separate cavity test is required, and at what pressure, is written in the order standard — the valve's own cavity relief is a design feature that the bench cannot verify.

Do you supply the adaptors for ball valves?

Yes — plate sets and adaptors for raised-face, ring-joint and weld-end connections are part of the quotation, and they are the part that decides how many valve families one bench covers. Wearing items such as sealing discs and clamping jaws are listed with their model mapping on the spare parts page.

Tell us the ball valve types, the DN range and the classes on your orders