How to test a globe valve — the direction is set by the design, and the gland is part of the result
A globe valve closes on one seat, in one direction, and the direction was chosen by whoever sized the valve — flow under the disc or over it. That makes the test sequence short compared with a gate valve, but it moves the attention to three places engineers get wrong: which side of the seat the pressure comes from, whether the disc is open far enough for the shell test, and what the gland does while the body is under pressure. This page is the sequence for flanged globe valves on a hydrostatic bench, from the flow arrow to the record.
Get a quotation Send the DN range, the flow convention on your drawings and the class you test to.
Quick answer
| Shell test | 1.5 × rating, disc cracked open so both sides of the seat fill |
| Seat test | 1.1 × rating, in the closing direction, disc seated by the stem |
| Direction | Set by the design — read the arrow, test the way the valve flows, record it |
| Gland | Under shell pressure — a gland weep is a finding, not something to tighten away |
| Backseat | Where fitted, a separate check — never a substitute for the main seat |
| Seating force | Normal handwheel force only — no cheater bars, no hammering the disc shut |
| After the test | Drain both sides, dry the seat, record the direction and the disc condition |
What is actually under pressure
“Test the globe valve” is two operations, like a check valve and unlike a gate or ball valve: one seat, so one seat test. What the globe valve adds is a stem that carries real force and a packing box that sits inside the shell pressure boundary. The shell test proves the body, the bonnet joint and the gland; the seat test proves the disc and the seat, loaded from the direction the line will load them. Everything on the record depends on getting the direction right first, because the same seat read from the other side is a different test with a different meaning.
| Test | What is under pressure | Disc position | What you read |
|---|---|---|---|
| Shell | Body, bonnet joint, gland, and the cavity on both sides of the seat | Cracked open — just off its seat | Casting seepage, bonnet bolts, gland weep — each noted separately |
| Seat, closing direction | Inlet side, loading the seat the way the design flows | Seated by the stem, normal handwheel force | Leakage past the seat, judged against the class named on the order |
| Backseat, where fitted | Stem backseated against the upper seating surface | Stem wound fully back onto the backseat | Packing area tightness in the backseated position — its own line |
| Stem packing | Part of the shell boundary on every globe valve | Any | A weep is a finding on the shell record, before anyone adjusts the gland |
The table explains the order of attention. On a gate valve the gland matters too, but the globe valve runs higher pressure drops across a smaller seat, so the thrust on the stem and the load on the packing are both larger at the same line pressure. A gland that held on a 16 MPa gate test may weep on the same pressure against a globe disc. That is information the customer paid for; the worst response is to screw the gland down mid-test and turn a finding into a hidden one.
Trap 1 — testing in the wrong direction
Flow under the disc or flow over the disc is not a detail on a globe valve — it decides which face of the seat the line pressure presses, how much force the stem sees when closing, and whether the packing is pushed out of the box or held in by pressure. The design was fixed when the valve was ordered, the arrow is cast or stamped on the body, and the seat test has to run from that side.
The failure mode looks innocent: the valve is clamped between two plates, the pump is connected to the nearer port, the reading looks clean, and the record says “seat test, 1.1 ×” with no direction. If the pressure came from the wrong port, the disc was pushed away from its seat instead of onto it, and the leakage you saw at the “outlet” is the valve passing water the way it was built to. The fix costs nothing: read the arrow before the first joint is made, connect the inlet to that side, and write the direction on the record beside the pressure — the same discipline the check valve page asks for, for the same reason.
Trap 2 — the shell test run through a closed disc
A closed globe disc divides the body exactly the way a closed check flap does: fill from the inlet and the upstream side climbs while the outlet side reads zero, and the half of the body beyond the seat never sees pressure. The shell test has not been done — it has been a seat preload exercise that also put the full shell pressure across a seating face that was never asked to hold it.
Crack the disc open — a quarter turn or the few turns that just lift the disc clear — so water crosses the seat and both sides equalise. Confirm the outlet-side gauge climbs with the inlet before starting the hold. On a soft-seated globe the point matters even more: holding shell pressure across a closed resilient seat is the same seat-damaging habit the by-valve-type page warns about for butterfly valves, and the damage does not appear until the valve is on the line.
Trap 3 — adjusting the gland during the test
The gland on a globe valve is a pressure boundary component, and the shell test is the only moment in the valve's workshop life when it is provably holding or provably leaking. A weep during the shell hold is a finding: it gets its own line on the record, beside the body reading, not folded into it and not wiped off. What it must not get is a spanner. Tightening the gland mid-hold turns a measurable state into an unmeasurable one — nobody can say afterwards whether the packing leaked because it was worn or because it was never adjusted in the first place.
The discipline is written into the sequence: the gland is checked — evenly, to the fitter's normal practice — before the valve goes on the bench, and then left alone for the whole test. If it weeps, the record says so and the valve goes to the packing station. If the order expects a re-test after adjustment, that re-test is a new hold with a new line, not a continuation of the first one.
Trap 4 — seating the disc with force it was not designed for
The seat test on a globe valve depends on how the disc was seated, and the only legitimate answer is: by the stem, with normal handwheel force, in the closing direction. A cheater bar on the handwheel, a hammer blow on the wheel spanner, or winding down on a disc that has already bottomed out does not improve the seal — it can flatten a resilient disc, brinell a metal seat face, or load the stem and packing in a way no line condition will reproduce.
Two practical rules keep the reading honest. First, seat the disc before pressurising and mark the handwheel position; if the leak reading is poor, re-seat once and record both attempts rather than leaning harder the second time. Second, remember what the pressure is doing for you: on a flow-under-the-disc design the line pressure itself presses the disc onto the seat, so a valve that weeps at low differential may hold at rated pressure — the same pressure-built-seal behaviour the leakage classes page explains, and the reason the class on the order names a minimum test pressure.
Trap 5 — calling the backseat the main seat
Many globe valves have a backseat: an upper seating surface the stem winds back onto, designed to isolate the packing from line pressure while the valve is open in service. It is a genuine feature and a genuine test — when the order asks for it. It is not the main seat test, and a tight backseat says nothing about the disc and seat at the bottom of the body.
The two are easy to confuse on the bench because both are read as “nothing coming out around the stem”. The difference is the disc position: backseated means the stem is wound fully back and the disc hangs open in the flow; main seat means the disc is closed by the stem. Run them as separate holds with separate lines on the record, and if the order does not mention the backseat, do not invent the test — it doubles hold time without adding a result anyone signed for.
Eight steps on the bench
- Read the flow arrow and the drawing convention. The arrow decides which fixture port is the inlet for both tests, and the direction goes on the record with every reading.
- Select the plates. Globe valves are almost always flanged — RF plates matched to the face, moderate daylight, and enough height clearance for the topworks and the handwheel.
- Mount with the gland accessible and the gland at its normal service adjustment. Check the bonnet bolts are even before anything is pressurised.
- Crack the disc open — just off its seat — and fill slowly from the low point with the vent open until water shows at the vent and the outlet-side gauge climbs with the inlet.
- Shell test at 1.5 × rating for the hold time the standard names. Watch the body, the bonnet joint and the gland; each gets its own observation, and the gland is not touched during the hold.
- Backseat check where the order asks: wind the stem fully back onto the backseat, re-pressurise, hold, record. Skip it when the order is silent.
- Seat test at 1.1 × rating from the inlet side, in the closing direction, disc seated by the stem with normal handwheel force. Read the leakage at the outlet against the class on the order.
- Drain both sides, dry the seat and the disc, and record the direction, the disc condition, the gland observation and the reading. Water left above a closed seat sits on it until the valve is packed.
What the bench must have for globe valve work
| Item | Why it matters on a globe valve |
|---|---|
| Fixed inlet on the flow side | The closing direction is set by the design, not by whichever port is nearer the pump |
| Height clearance for the topworks | Globe valves are tall; the handwheel and yoke must clear the frame at full travel |
| Gland access during the hold | The gland is observed, not adjusted — the fitter has to see it for the whole shell hold |
| Two gauges across the range | A 1.1 × PN10 seat test is read on a low-range gauge; a 40 MPa dial cannot resolve it |
| Gauge on both sides | Both sides must climb together for the shell test to be real; the seat test reads the outlet |
| Low-pressure, high-flow fill | Large PN10 and PN16 bodies need litres per minute; the fill is slow and vented like any hydrostatic test |
| Drain on both sides | The shell test leaves water on both faces of the seat; the seat test leaves it upstream |
Which of our machines come up for globe valve work
The range is built around the bore first, and globe valves sit across the whole envelope — small high-pressure globes at one end, large low-pressure bodies at the other. The numbers below are the published envelopes of each model, not a recommendation for a specific valve:
| Model | Layout | DN range | Test pressure | Clamping | Why it is on this list |
|---|---|---|---|---|---|
| ZSYJ-300A | Vertical, single station | DN50–DN300 | 1.6–40 MPa | 80 t | Small and mid-size flanged globes, including the high-pressure small-bore end |
| SYJ-600SQ | Vertical, water + air | DN50–DN600 | 40 MPa water / 4 MPa air | 90 t | Shell and seat plus a low-pressure air bubble check on the same frame |
| SYJ2-300-600 | Two stations | DN50–300 and DN350–600 | PN6–PN100 | One clamp per station | Small globes and large globes in the same shift without re-rigging |
| WBD-600 | Horizontal, ram + 3 jaws | DN50–DN600 | 0–16 MPa | 150 t | Large bodies that lie flat, with the topworks and handwheel clear of the frame |
| SYJ-600M | Vertical clamp | DN350–DN600 | 0–10 MPa | 126 t | Large low-pressure bodies in a workshop where crane height is limited |
Selection by size is worked through on the DN selection page, and the pressure numbers that go with each class are on the test pressure chart. Fixtures — plate sets, spacers, sealing discs and jaw inserts — are quoted with the machine and listed by model on the spare parts page.
Where a globe valve differs from the gate valve on the next bench
The two families share a rising stem, a gland and a flanged body, and the work instructions still differ on three points. The gate valve has two seats and gets a seat test in each direction; the globe valve has one seat and gets one seat test, in the closing direction the design fixed. The gate valve is tested half open for the shell test through an open gate; the globe valve is tested with the disc cracked open through the seat — a small difference in position with the same purpose, filling the whole cavity. And the globe gland carries more load at the same pressure, because the disc turns the full line pressure into stem thrust, so the gland observation during the shell hold is a first-class result on a globe record in a way it rarely is on a gate record.
The gate sequence is written out in how to test a gate valve, the ball valve sequence — including the cavity question — in how to test a ball valve, and the butterfly sequence in how to test a butterfly valve. The fixture side of the problem is in clamping methods, and the general order of operations that keeps any reading valid is in the 8-step procedure. The leakage classes that decide what the outlet reading means are on the leakage rate classes page.
Boundaries worth writing down
The bench does not declare the valve compliant. It produces a pressure record and a leakage observation. Whether that satisfies API 598, ISO 5208, EN 12266-1 or GB/T 13927 is a judgement made by your quality function or the inspector named on the order.
The direction is part of the result. A seat reading without the flow direction written beside it cannot be compared with the order, because the same seat reads differently from each side. The arrow decides the inlet; the record keeps the proof.
Seating force is operator discipline. The disc is seated by the stem with normal handwheel force. Bars, hammers and extra turns change the seating geometry and can damage a seat that would have passed.
The backseat is not the main seat. Where fitted, it is a separate characteristic tested only when the order asks, and it never substitutes for the disc-and-seat test at the bottom of the body.
The envelope is mechanical. A 16 MPa bench does not become 25 MPa through a larger pump or a different gauge, and height clearance for tall topworks is a fixture question solved at the quotation stage, not on the shop floor.
Questions we get asked about globe valves
Which direction do I test a globe valve in?
In the closing direction, from the side the design flows — under the disc or over it, as the arrow on the body and the order drawing say. The disc is seated by the stem and the pressure loads the seat the way the line will. The direction is written on the record beside every reading, because the same seat read from the other side is a different test.
Open or closed disc for the shell test?
Cracked open — just off its seat. A closed disc divides the body: the outlet side and the cavity beyond the seat never see pressure, and the shell test is not actually done. On a soft-seated globe, holding shell pressure across a closed resilient seat is also how a good seat gets damaged before the valve ships.
The gland weeps during the shell test — do I tighten it?
Not during the hold. A gland weep is a finding: it gets its own line on the shell record. Tightening the gland mid-test turns a measurable state into an unmeasurable one — nobody can tell afterwards whether the packing was worn or simply never adjusted. The gland is set to normal service adjustment before the valve goes on the bench and left alone for the whole test.
What is the backseat, and do I have to test it?
The backseat is the upper seating surface the stem winds back onto, where the design has one. It isolates the packing while the valve is open in service. It is tested only when the purchase order or the product standard asks, as a separate hold with its own line — and it is never a substitute for the main seat test on the disc.
How hard should I close it for the seat test?
Normal handwheel force, by the stem, and stop. Cheater bars and hammer blows flatten resilient discs and brinell metal seats, and the damage does not show until the valve is on the line. If the first reading is poor, re-seat once with the same force and record both attempts instead of leaning harder.
My globe valve weeps at low pressure but holds at rated pressure. Is the seat bad?
Often no. On a flow-under-the-disc design the line pressure itself presses the disc onto the seat, so at very low differential there is little force making the seal and a few drops can pass. The standard or the order names a minimum seat test pressure for exactly this reason — read the result at the specified pressure and the class on the order before rejecting anything.